Fibre optic cable buying guide

A fibre cable order is defined by five choices: fibre type, cable type, core count, connectors and the test data that comes with each drum. This guide sets them out in the order a spec sheet fixes them; send a brief once they are clear.

Request a quote

Fibre optic cable buying guide scene: loose tube cable end, coloured fibres and LC and SC patch cords on a test bench

Choice 1: the fibre

Single-mode fibre to ITU-T G.652.D is the default for access, metro and long-haul networks: 125 um cladding with a coating of about 242 um, or 200 um in reduced-diameter versions. Bend-insensitive G.657 fibre is used where routes are tight, such as FTTH drops, risers and indoor boxes. G.657.A1 allows a minimum bend radius of 10 mm, A2 and B2 7.5 mm and B3 5 mm, and the A category is compatible with G.652.D, so it can be spliced into the same network. Multimode fibre stays inside buildings and data centres: OM3, OM4 and OM5 are 50/125 um fibres graded by effective modal bandwidth at 850 nm of at least 2,000 MHz.km for OM3 and 4,700 MHz.km for OM4; OM5 adds a 953 nm specification of 2,470 MHz.km for wavelength-division links. For 10G Ethernet over OM4, 400 m is the distance commonly quoted for IEEE 10GBASE-SR.

Attenuation values are given per datasheet for the fibre and cable you order. Where no cable figure is available, older TIA-568 planning values are often used: 3.5 dB/km at 850 nm and 1.5 dB/km at 1300 nm for multimode, 1.0 dB/km indoor and 0.5 dB/km outdoor for single-mode, 0.75 dB per mated connector pair and 0.3 dB per splice. Use the cable maker's spec where available. See optical fibre.

Choice 2: the cable

Fibre cable types and where they are used
Cable typeConstructionTypical coresMain use
Indoor tight-buffered0.9 mm tight buffers, aramid yarn, PVC or LSZH jacket2-144Risers, floors, equipment rooms
Outdoor loose tubeGel-filled tubes, central strength member, PSP or APL tape, PE sheath2-288Duct, aerial lashed, armoured for burial
ADSS aerialLoose tubes on a central FRP, aramid strength, PE or AT sheathPer span designPole lines and power line routes
FTTH dropG.657 fibres, FRP or steel strength members, LSZH jacket1-2Last drop into the premises
Patch cords2.0 or 3.0 mm jacket, SC or LC1-2Panels, ONTs, equipment

The 24-core GYTS reference is about 10 mm in diameter, but weight varies by around 50% between makers, so weight is always taken per datasheet. ADSS must be selected for the span and the weather loading: a cable that suits a 100 m span may only manage about 50 m in heavy ice. Sheath choice between PE and anti-tracking AT depends on the field strength along the line, calculated for the route. In the EU, fibre cable permanently installed in buildings falls under EN 50575 and needs a CPR class; in the US, NEC 770 grades such as OFNR and OFNP apply.

Choice 3: the core count

Count the fibres needed on day one, add spares for repairs and growth, then round up to the nearest standard tube count. Loose tube cables are built from tubes of a fixed fibre count, so a 24-core and a 48-core cable may differ only in the number of tubes, while the jump to a larger tube design can change diameter and drum length. Fibres and tubes are identified by the TIA-598 colour code unless your network uses another scheme, which must be written on the spec sheet. See fibre cable core counts.

Drum length belongs in the same decision. Outdoor and ADSS cable commonly ships on 2 km or 4 km drums and drop cable on 1 km reels, but the right length is the one that matches your splice points, so that crews do not cut short ends off every drum. Give the route lengths or the splice plan and the desk sets the drum plan with the plant before production, with start and end metre marks recorded for every drum.

Choice 4: connectors and polish

SC and LC are the common single-mode connectors; LC dominates in high-density panels. UPC polish suits most data links, while APC is used where back-reflection matters, such as FTTH and video overlays. IEC 61753-1 sets the grades: Grade B random-mated insertion loss averages 0.12 dB or less with 97% of matings at 0.25 dB or less, Grade C averages 0.25 dB or less, and return loss is at least 60 dB for Grade 1 (APC) and 45 dB for Grade 2 (UPC). State the grade you need rather than asking for low loss.

Choice 5: test data

  • Attenuation per fibre at the agreed wavelengths, listed by drum and fibre colour.
  • OTDR traces for each fibre on each drum, so that splicing crews can compare after installation.
  • Insertion and return loss for every patch cord or pigtail, against the IEC 61753-1 grade.
  • Drum ledger: drum number, length, start and end metre marks and fibre count, matched to the packing list.

Outdoor cable is commonly built to Telcordia GR-20 and indoor cable to GR-409; ask the plant which reports cover your construction. Fibre and fibre cable are mainly sourced from Wuhan Optics Valley and Qidu in Wujiang. Lead time is set by fibre and tube scheduling and confirmed in writing for each order; see MOQ and lead time.

Questions buyers ask

Q01Should I choose G.652.D or G.657 fibre?

Use G.652.D for most outdoor and backbone cable. Choose G.657 where bends are tight, such as drops, risers and indoor boxes. G.657.A fibres are compatible with G.652.D, so they can be spliced into the same network.

Q02What is the difference between OM3 and OM4?

Both are 50/125 um multimode fibres. OM4 has a higher effective modal bandwidth at 850 nm, at least 4,700 MHz.km against 2,000 for OM3, which allows longer links. For 10GBASE-SR over OM4, 400 m is the distance commonly quoted.

Q03What test data should come with fibre cable?

Attenuation per fibre at the agreed wavelengths and OTDR traces for each fibre on each drum, plus insertion and return loss for patch cords. The desk matches the records to drum numbers and the packing list before loading.

Q04Can ADSS be bought by span length alone?

No. ADSS is selected for span length together with wind and ice loading and, for the sheath, the electric field along the power line. A design suiting 100 m in mild weather may only manage about 50 m in heavy ice, per maker data.

RFQSend the construction or standard you need, cross-sections, total metres and drum lengths, the reports your market asks for and the destination port. The desk replies in writing with matched factories, a spec sheet and the reference MOQ.