Power cable buying guide

Six decisions shape most power cable orders, and each one changes price, weight and lead time. This guide walks through them, then lists the spec sheet fields and the routine tests to ask for on every drum before you send a brief.

Request a quote

Power cable buying guide scene: drums of armoured and XLPE power cable with a spec sheet and test record on a clipboard

Decision 1: low or medium voltage

Low voltage power cable at 0.6/1 kV covers feeders and sub-mains in buildings, plants and solar balance of system; the rating means 0.6 kV to earth and 1 kV between conductors, with 1.2 kV as the highest system voltage. Medium voltage cable to IEC 60502-2 runs in classes 3.6/6, 6/10, 8.7/15, 12/20 and 18/30 kV and adds a conductor screen, insulation screen and copper tape screen around thicker XLPE. The partner plant catalogue behind our MV reference reaches 8.7/15 kV; higher classes are matched to other plants. MV adds process steps and partial discharge testing, which affects lead time.

Decision 2: armoured or unarmoured

Armour protects against mechanical damage in burial, trenches and industrial routes; it does not make a cable suitable for heavy pulling tension. Multicore cable usually takes steel wire armour (SWA), to BS 5467 with a PVC sheath or BS 6724 with LSZH in the UK. AC single-core cable uses aluminium wire armour (AWA) to avoid eddy-current heating. Steel tape armour (STA) is also an allowed form in IEC 60502-1 and is what our armoured reference uses. Armour adds weight: the 4x35 mm2 STA reference is about 2,067 kg/km.

Decision 3: copper or aluminium

Aluminium conductors cut weight and metal cost on large feeders. The 4x95 mm2 aluminium reference weighs about 1,907 kg/km, and its IEC 60228 limit of 0.320 ohm/km is close to copper 50 mm2, so an aluminium cable is usually upsized by your engineer. Small aluminium sizes are not offered; multicore aluminium typically starts at 10 mm2. Terminations, lugs and local rules must suit aluminium.

Decision 4: fire performance

Three properties are often confused. Flame retardance is tested to IEC 60332-1-2 on a single cable or IEC 60332-3 on bunched cables. Low smoke zero halogen behaviour is tested to IEC 61034 and IEC 60754-1/-2. Circuit integrity, keeping power on during a fire, is tested to IEC 60331, BS 6387 CWZ or BS 8519. In the EU, cable permanently installed in buildings also needs a CPR class declared on the DoP, which describes reaction to fire only. Ask for each property by name, per test report; see fire-resistant cables.

Decision 5: solar DC cable

Solar strings use single-core cable such as H1Z2Z2-K to EN 50618 and IEC 62930, with tinned Class 5 copper and cross-linked halogen-free insulation and sheath, rated DC 1.5 kV; US projects use UL 4703 PV Wire. PV1-F has been superseded by H1Z2Z2-K. Coils of 100 m and 500 m drums are usual; see solar PV cables.

Decision 6: market and standard

Pick the standard before the plant. IEC 60502-1 suits most export markets; the UK, US, Thailand, South Africa and Saudi Arabia have their own routes, listed in the cable standards guide. A construction that is correct to IEC 60502-1 may still be refused on a UK site that specifies BS 6724, or on a US job where the AHJ expects UL-listed products. The plant must hold the reports or listing for that exact construction and size range, so the desk checks the certificate scope before shortlisting rather than after a sample has been made.

Write down the cluster preference only if it matters to you. Power and special cables are made mainly in Yixing and Guanlin, Ningjin and Wuwei; the desk shortlists by construction, standard and test capability, which often matters more than location.

Spec sheet fields to fix in writing

Power cable spec sheet fields
FieldExample entryWhy it matters
Voltage and standard0.6/1 kV, IEC 60502-1Sets insulation thickness and tests
Cores and size4x25 mm2 or 3x95+1x50 mm2Basis of copper weight and price
ConductorAnnealed copper, Class 2, IEC 60228Resistance limit used for checks
InsulationXLPE, nominal thickness per standardTemperature rating and cost
Armour and screenSTA, SWA, AWA, copper tape or noneWeight, earthing, lead time
SheathPVC, LSZH or PE; colourFire tests, UV and site rules
Fire propertiesIEC 60332-1-2; CPR class on the DoPWhich reports must exist
MarkingBrand, construction, standard, year, metre marksChecked on every drum
Drum planLength per drum, drum type, end capsSite pulls and freight weight

Routine tests to ask for per drum

  • Conductor DC resistance at 20 C against IEC 60228.
  • Spark test or voltage test on insulation and sheath; for MV, the IEC 60502-2 routine test at 3.5 U0 for 5 minutes.
  • Partial discharge for MV, at 1.73 U0 with sensitivity of 10 pC or better, method to IEC 60885-3.
  • Dimensions: insulation and sheath thickness and overall diameter, on sample tests.
  • Print and metre marks against the agreed text, and drum length against the ledger.

Type tests such as thermal ageing and fire tests sit in the plant's reports; the desk checks which constructions and dates they cover. Typical MOQs are on MOQ and lead time.

Questions buyers ask

Q01Do I need armoured cable for direct burial?

Usually yes, or a cable your wiring rules accept for burial. Armour resists mechanical damage but not heavy pulling tension. Use SWA for multicore and AWA for AC single core; your project engineer and local rules decide.

Q02Is LSZH the same as fire-resistant cable?

No. LSZH describes low smoke and halogen-free behaviour, tested to IEC 61034 and IEC 60754. Fire-resistant means circuit integrity during a fire, tested to IEC 60331, BS 6387 or BS 8519. A cable can have one property without the other.

Q03What tests come with each drum?

Routine records normally cover conductor resistance and a spark or voltage test, plus partial discharge for medium voltage cable. The desk collects them per drum, matches them to the drum ledger and checks type test reports for the construction.

Q04Can I switch from copper to aluminium to save cost?

Often, for large feeders, but the size usually increases because aluminium has higher resistance. Your engineer must recalculate the size and confirm terminations; the desk then sources the aluminium construction to IEC 60228 Class 2.

RFQSend the construction or standard you need, cross-sections, total metres and drum lengths, the reports your market asks for and the destination port. The desk replies in writing with matched factories, a spec sheet and the reference MOQ.