Cable conductor materials: copper, aluminium and IEC 60228 classes

The conductor sets most of a cable's price and weight, and it is where short cross-sections hide. This page covers copper against aluminium, the IEC 60228 classes and the resistance test that proves a size.

Request a quote

Stranded copper and aluminium cable conductors cut square to compare conductor materials and strand counts

What the conductor does and how it is classified

The conductor carries the current, and its cross-section sets resistance, heat and voltage drop. IEC 60228 does not define a conductor by its strand count or diameter but by its maximum DC resistance at 20 C. A cable sold as 25 mm2 copper is correct if its resistance is no higher than the limit for that size and class; that single number is the buyer's best check.

The standard groups conductors into four classes. Class 1 is solid, used for small building wire such as H07V-U. Class 2 is stranded, the normal choice for power cable and H07V-R. Class 5 is flexible, made of many fine wires, used in cords, H07V-K and solar cable. Class 6 is more flexible again, for moving applications. The finer the strands, the more flexible the cable and, for the same nominal size, the slightly higher the permitted resistance.

Resistance limits buyers can check

The table lists maximum DC resistance at 20 C from IEC 60228 for common sizes. Compare these with the figure on each drum's test record.

IEC 60228 maximum DC resistance at 20 C, ohm/km
Size, mm2Copper Class 1/2Copper Class 5, plainCopper Class 5, tinnedAluminium Class 2
2.57.417.98--
44.614.955.09-
63.083.303.39-
101.83--3.08
250.727--1.20
500.387--0.641
950.193--0.320
1200.153--0.253

The partner plant catalogue behind our reference constructions lists 0.727 ohm/km for the 4x25 mm2 copper XLPE cable and 0.320 ohm/km for the 4x95 mm2 aluminium cable, both matching the limits. The tinned Class 5 figure of 5.09 ohm/km for 4 mm2 is the one to check on H1Z2Z2-K solar cable.

Copper or aluminium

Aluminium has higher resistance than copper for the same size, so it is usually specified one or two sizes larger. Reading the table, aluminium 120 mm2 at 0.253 ohm/km sits close to copper 70 mm2 at 0.268 ohm/km, though the final size is set by the project engineer under IEC 60364-5-52, BS 7671 or NEC as applicable. Aluminium is lighter and its metal is cheaper, which is why utilities and large feeders use it. The trade-offs are larger diameter, joints and lugs rated for aluminium, and the fact that plants do not supply small aluminium sizes: the reference catalogue starts at 10 mm2. In the US, NEC sets 14 AWG as the minimum copper size and 12 AWG for aluminium or copper-clad aluminium. See aluminium cables for constructions.

  • Plain annealed copper: the default for building wire, power, control and data cable.
  • Tinned copper: Class 5 for solar cable, with single wires of no more than 0.31 mm in the reference H1Z2Z2-K; also used where corrosion is a concern.
  • Aluminium Class 2: LV and MV feeders from 10 mm2 upward, round stranded in the reference 4x95 mm2 construction.

Short cross-sections and CCA

Two conductor risks recur. The first is an undersized conductor: BASEC has warned of SWA cable whose effective cross-section was up to two sizes below the marked size, with both conductor and armour resistance out of limit. The second is copper-clad aluminium sold as copper. CCA is about 30 percent lighter, shows aluminium when the strand is scraped, and can be identified by XRF. Category network cable requires solid copper conductors, so a Cat6 cable with CCA conductors does not meet the category. The desk does not offer CCA as a data cable option; read more in CCA vs copper.

What changes price, weight and lead time

Copper and aluminium make up roughly 80 percent of product cost according to listed cable makers' filings, and Chinese quotes are normally metal price plus a processing fee. LME three-month copper reached a record of USD 14,875 per tonne intraday on 10 September 2026 (Fastmarkets) and was around USD 14,315 per tonne on 21 October 2026, which is why quote validity is counted in days and long projects use a copper adjustment formula. Weight follows the metal: the reference 4x25 mm2 copper cable weighs about 1,292 kg/km. Lead time starts when copper is booked against the agreed quote; see cable pricing guide and MOQ and lead time.

How the desk checks conductors

  1. The spec sheet names metal, class, size and, for tinned or compacted conductors, the finish.
  2. Each drum's test record shows DC resistance at 20 C, compared with the IEC 60228 limit.
  3. At pre-shipment inspection a sample end is cut, strands are counted and scraped, and weight per metre is compared with the datasheet.
  4. Any deviation is raised with the plant before loading, not after arrival. Send your sizes through the quote form.

Questions buyers ask

Q01How do I know a cable is the size printed on it?

Ask for the conductor DC resistance at 20 C on each drum and compare it with the IEC 60228 limit, for example 0.727 ohm/km for 25 mm2 copper Class 2. A resistance above the limit means the copper is short, whatever the print says.

Q02Is aluminium cable a lower grade product?

No. Aluminium Class 2 conductors are covered by IEC 60228 and widely used in feeders and distribution. They need a larger size than copper for the same resistance, joints rated for aluminium, and are not offered in small sizes.

Q03When should I specify tinned copper?

Tinned Class 5 copper is required in EN 50618 solar cable such as H1Z2Z2-K and is common where moisture or corrosion is a concern. Check the tinned resistance limit, for example 5.09 ohm/km for 4 mm2.

Q04Can CCA be used for network cable?

Category cable requires solid copper conductors, so CCA conductors do not meet Cat5e or Cat6. CCA is about 30 percent lighter than copper, shows aluminium when scraped and can be confirmed with XRF.

Q05Why does my cable quote expire so quickly?

Metal is most of the cost and copper moves daily on the LME. Plants price as metal plus processing fee, so validity is counted in days. Long projects can use a copper adjustment formula agreed in writing.

RFQSend the construction or standard you need, cross-sections, total metres and drum lengths, the reports your market asks for and the destination port. The desk replies in writing with matched factories, a spec sheet and the reference MOQ.